How does the cooling system of the power transformer work?

The cooling system of main transformer is OWDF forced oil circulating cooling system, which is used to cool the insulating oil of transformer. It mainly includes: submersible oil pump, cooler, flowmeter, leak detector, inlet and outlet hydraulic valve, inlet and outlet pressure gauge, total inlet water flow meter, outlet water flow meter, outlet water temperature meter, etc. The cooler oil pipe is installed at the upper and lower parts of the transformer body. During normal operation, the submersible oil pump sends the insulating oil of the main transformer to the cooler from the top of the transformer, and then flows to the lower part of the transformer from the oil drain pipe of the transformer. In the cooler, the cooling water flows through the water pipe of the cooler, and the oil and water conduct heat exchange to reduce the oil temperature of the main transformer. A flow of oil is formed in the transformer from bottom to top. When the oil flows through each element, the insulating oil of the main transformer exchanges heat with the heating element to cool the transformer.

The cooler is composed of cooling oil chamber, cooling water pipe, upper and lower water chambers and water leakage detector. The cooling water pipe is composed of 36 double-layer copper pipes. The outer tube is a spiral pneumatic tube with high thermal conductivity, good compression resistance and impact resistance; The inner pipe is a kind of corrosion resistant bare pipe with strong corrosion resistance. The double-layer copper pipe is fixed on the upper and lower flanges after being “expanded” to connect the space between the double-layer copper pipe and the fixed flange cavity. It is fixed at the upper and lower ends of the oil chamber of the cooler. The water chambers at the lower end of the cooler are separated from each other, and are respectively water inlet and outlet chambers.

The cooling water flow in the cooler can be adjusted by adjusting the inlet and outlet valves of the cooler. When the wall of double layer cooling water pipe breaks, water or oil will flow from the damaged part to the double layer water pipe, and flow to the water leakage detector through space at the lowest point, The electric contact is connected and sends a water leakage signal from the cooler.

How does the cooling system of the power transformer work?-SPL-電力変圧器、電気変圧器、複合コンパクト変電所、金属被覆AC密閉型スイッチギア、低電圧スイッチギア、屋内AC金属被覆中間スイッチギア、非カプセル化乾式電力変圧器、非包装コイル乾式変圧器、エポキシ樹脂鋳造シリコン鋼板乾式変圧器、エポキシ樹脂キャストアモルファス合金乾式変圧器、アモルファス合金油浸電力変圧器、シリコン鋼板油浸電力、電気変圧器、配電用変圧器、降圧変圧器、還元変圧器、低-損失電力変圧器、損失電力変圧器、油型変圧器、油分配変圧器、変圧器-油浸変圧器、油変圧器、油浸変圧器、三相油浸電力変圧器、油充填電気変圧器、密封アモルファス合金電力変圧器、乾式変圧器、乾式変圧器、鋳造樹脂乾式変圧器、乾式変圧器、樹脂鋳造型変圧器、樹脂製乾式変圧器、CR DT、アンラップコイル電力変圧器、三相乾式変圧器、関節式ユニット変電所、AS、モジュラー変電所、変圧器変電所、電気変電所、電力変電所、プレインストール変電所、YBM、プレハブ変電所、配電変電所、コンパクト変電所、MV変電所、 LV発電所、HV発電所、スイッチギアキャビネット、MVスイッチギアキャビネット、LVスイッチギアキャビネット、HVスイッチギアキャビネット、引き出し式スイッチキャビネット、Ac金属閉リングネットワークスイッチギア、屋内金属装甲中央スイッチギア、ボックス型変電所、カスタム変電所、カスタマイズされた変圧器、金属封入電気スイッチギア、LVスイッチギアキャビネット、