Why should transformer instantaneous protection avoid low-voltage short-circuit current?

Why should transformer instantaneous protection avoid low-voltage short-circuit current?-SPL- power transformer,electrical transformer,Combined compact substation,Metalclad AC Enclosed Switchgear,Low Voltage Switchgear,Indoor AC Metal Clad Intermediate Switchgear,Non-encapsulated Dry-type Power Transformer,Unwrapped coil dry-type transformer,Epoxy resin cast silicon steel sheet dry-type transformer,Epoxy resin cast amorphous alloy dry-type transformer,Amorphous alloy oil-immersed power transformer,Silicon steel sheet oil-immersed power,electric transformer,Distribution Transformer,voltage transformer,step-down transformer,reducing transformer,low-loss power transformer,loss power transformer,Oil-type Transformer,Oil Distribution Transformer,Transformer-Oil-lmmersed,Oil Transformer,Oil Immersed Transformer,three phase oil immersed power transformer,oil filled electrical transformer,Sealed amorphous alloy power transformer,Dry Type Transformer,dry Transformer,Cast Resin Dry Type Transformer,dry-type transformer,resin-casting type transformer,resinated dry type transformer,CRDT,Unwrapped coil power transformer,three phase dry Transformer,articulated unit substation,AS,Modular substation,transformer substation,electric substation,Power Sub-station,Preinstalled substation,YBM,prefabricated substation,Distribution Substation,compact substation,MV power stations,LV power stations,HV power stations,Switchgear Cabinet,MV Switchgear Cabinet,LV Switchgear Cabinet,HV Switchgear Cabinet,pull-out switch cabinet,Ac metal closed ring network switchgear,Indoor metal armored central switchgear,Box-type substation,custom transformers,customized transformers,Metal enclosed electrical switchgear,LV Switchgear Cabinet,

This is mainly to consider the selectivity of transformer relay protection action. The quick break protection at the high voltase side of the transformer is mainly used to protect the external faults of the transformer. In the setting, if the maximum short circuit current at the low voltase side of the transformer is not avoided, the short circuit current values in the range not far from the outlet at the low voltage side do not change much and are basically the same, which will expand the scope of the quick break protection at the high voltage side of the transformer to the low-voltage outgoing line, thus losing the selectivity After the loss of selectivity, the protection is more reliable, but it brings inconvenience to permission. For example, many industrial parks are now equipped with 10KV general distribution rooms (10KV bus bars+outgoing circuit breakers), and each workshop is equipped with low-voltage distribution rooms (ring network cabinet+transformer). If the circuit breaker does not escape the maximum short circuit current at the low-voltage side of the transformer, it will cause the low-voltage main switch, (ring network cabinet load switch fuse), and high-voltage circuit breaker to act, which will bring inconvenience to the operation