Vacuum transformer oil filter device

Vacuum transformer oil filter device-SPL- power transformer, distribution transformer, oil immersed transformer, dry type transformer, cast coil transformer, ground mounted transformer, resin insulated transformer, oil cooled transformer, substation transformer, switchgear

Vacuum transformer oil filter device

 

Have been tested by us for 7 years to be the most cost-effectirve among different modles of Vacuum oil filter device. We can help you to derease the risk of transformer manufacturing equipment selection, especially for a new transformer factory.


Descriptions

There are great hazards, which are described as follows:

1. Reduce the breakdown voltage of the oil. The water content in the insulating oil is the main reason that affects the breakdown voltage reduction.

2. It will increase the dielectric loss factor. Because the presence of water in the oil is different, the influence on the dielectric loss factor is also different. The suspended emulsified water will increase the dielectric loss of the oil most obviously. Corrosion products of water, such as

Naphthenic acid soaps are very easy to worsen the dielectric loss and will sharply increase the dielectric loss, which is the indirect result of moisture affecting the dielectric loss

Fruit.

3. Make the insulating fiber easy to age and increase its dielectric loss.

4. Water promotes the corrosion ability of organic acids and accelerates the corrosion of metal parts. Metal corrosion products

Metal soaps, for example, will promote the rapid aging of oil, that is, play a catalytic role in oil aging,

To sum up, the more water content in the oil, the aging of the oil itself, the aging of equipment insulation and the corrosion of metal parts

The faster the corrosion rate is, it will affect the safe operation of the equipment and shorten the service life of the equipment.

Tech Data

Performance index unit high-efficiency two-stage vacuum oil filter

Flow L/h 3000

Two-stage vacuum system composed of vacuum stage vacuum pump and Roots pump

Working vacuum Pa ≤ 133

Limit vacuum pa ≤ 5

Constant temperature control range ℃ 20~80

Working pressure MPa ≤ 0.5

Working voice dB (A) ≤ 75

Pumping rate of vacuum unit ㎡/h ≥ 1000

Continuous working hours ≥ 200

Fault free working hours ≥ 5000

Overall leakage rate of unit Pa * L/s ≤ 100

Heating power KW 30 (two sets of independent heaters can be selected according to actual needs

Select one or two groups of work)

Total power KW 33

Power supply three-phase four-wire 380V50Hz

Inlet and outlet pipe diameter mm Ф thirty-two

Overall dimension

Length mm 1500

Width mm 1000

Height mm 1600

Equipment weight kg 500

Indicator after treatment

Residual moisture after filtration ppm ≤ 5 (GB/T260)

Residual gas% ≤ 0.1

Filtering precision μ M ≤ 1, no free carbon

Mechanical impurities% None (GB/T511)

Breakdown voltage KV ≥ 60

Cleanliness ≤ Class 6 (NAS1638)

Flash point (closed) ℃ ≥ 135 (GB/T3536)

Acetylene% 0